Conventional Photoelectric Smoke Detector

New product

The PS-24 photoelectric smoke detector utilizes two bi-colored LED's for indication of status. In a normal standby condition the LED's flash green every 3 seconds. When the detector senses that its sensitivity has drifted outside the UL listed sensitivity window the LED's will flash red every 3 seconds. When the detector senses smoke and goes into alarm the status LED's will latch on red.

The detector utilizes an infrared LED light source and silicon photo diode receiving element in the smoke chamber. In a normal standby condition, the receiving element receives no light from the pulsing LED light source. In the event of a fire, smoke enters the detector smoke chamber and light is reflected from the smoke particles to the receiving element. The light received is converted into an electronic signal.

  • Low profile, 1.8” high (with base) 
  • 2 or 4 wire base compatibility, relay bases available 
  • Highly stable operation, RF/Transient protection 
  • Low standby current, 45 µA at 24 VDC
  • Two built-in power/sensitivity supervision/alarm LED’s 
  • Non-directional smoke chamber 
  • Vandal resistant security locking feature 
  • Built-in magnetic go/no go detector test feature 
  • Removable smoke labyrinth for cleaning or replacement 
  • Automatic Sensitivity window verification function meets outlined requirements in NFPA 72, Chapter 7, Inspection, Testing and Maintenance.
  • Compatible with IS-24 ionization detectors 
  • Backwards compatible with Potter PS and IS detectors. 
  • Compatible with Potter releasing controls 

8 other products in the same category: